Home Fire Sprinklers Fire Alarms Fire Extinguishers Fire Suppression  

Fire Alarm Services

Florida Fire Service, Inc.

Fire Alarms Tampa

Tampa Fire Alarms
Tampa Fire Alarms

Class A, B, C and D Fires
Class A, B, C and D Fires

Tampa NFPA 72 Fire Alarm Code

Tampa NFPA 72 Fire Alarm Inspections, Tests and Maintenance

Residential, commercial and industrial fire protection systems may also be required by state, city and municipal health, building and fire codes to have all installed fire protection systems tested and inspected by local fire departments, state licensed fire protection companies, certified fire protection technicians and/or fire safety engineers.Keeping your fire alarm system operating and ready in case of an emergency.

Check with your local fire marshall, fire departments or city municipalities health, building and fire codes for details.

Visit NFPA 72: National Fire Alarm and Signaling Code to purchase most recent version. Tampa NFPA Standards and Codes

Table 10.4.3 - Testing Frequencies

  COMPONENT  FLITIAL/ REACCEPTANCE MONTHLY QUARTERLY SEMI-ANNUALLY ANNUALLY
1 Control Equipment - Building systems connected to supervising station   
  a) Functions 
  b) Fuses 
  c) Interfaced equipment 
  d) Lamps and LEDs 
  e) Primary (main) power supply 
  f) Transponders 
   
2 Control equipment - Building systems not connected to supervising station   
  a) Functions 
  b) Fuses 
  c) Interfaced equipment 
  d) Lamps and LEDs 
  e) Primary (main) power supply 
  f) Transponders 
   
3 Engine-driven generator - Central station facilities and fire alarm systems 
   
4 Engine-driven generator - Public fire alarm reporting systems  X (weekly) 
   
   
  COMPONENT  FLITIAL/ REACCEPTANCE MONTHLY  QUARTERLY  SEMI- ANNUALLY  ANNUALLY 
5 Batteries - Central station facilities   
  a) Lead-acid type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
  4. Specific gravity 
  b) Nickel-cadmium type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
  c) Sealed lead-acid type 
  1. Charger test (replace battery within 5 years after manufacture or more frequently as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
   
6 Batteries - Fire alarm systems   
  a) Lead-acid type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
  4. Specific gravity 
  b) Nickel-cadmium type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
  c) Primary type (dry cell)   
  1. Load voltage test 
  d) Sealed lead-acid type   
  1. Charger test (replace battery within 5 years after manufacture or more frequently as needed) 
  2. Discharge test (30 minutes) 
  3. Load voltage test 
   
7 Batteries - Public fire alarm reporting systems  X (daily) 
(From street locations to the communications center)
  a) Lead-acid type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (2 hours) 
  3. Load voltage test 
  4. Specific gravity 
  b) Nickel-cadmium type   
  1. Charger test (replace battery as needed) 
  2. Discharge test (2 hours) 
  3. Load voltage test 
   
   
  COMPONENT  FLITIAL/ REACCEPTANCE MONTHLY  QUARTERLY  SEMI- ANNUALLY  ANNUALLY 
  c) Sealed lead-acid type   
  1. Charger test (replace battery within 5 years after manufacture or more frequently as needed) 
  2. Discharge test (2 hours) 
  3. Load voltage test 
8 Fiber-Optic Cable Power 
   
9 Control Unit Trouble Signals 
   
10 Conductors - Metallic 
   
11 Conductors - Nonmetallic 
   
12 Emergency Voice / Alarm Communications Equipment 
   
13 Retransmission Equipment 
   
14 Remote Annunciators 
   
15 Initiating Devices   
  a) Duct detectors 
  b) Electromechanical releasing device 
  c) Fire extinguishing system(s) or suppression system(s) switches 
  d) Fire-gas and other detectors 
  e) Heat detectors 
  f) Fire alarm boxes 
  g) Radiant energy fire detectors 
  h) System smoke detectors - functional 
  i) Smoke detectors - sensitivity  X - - - X
  j) Single and multiple-station smoke alarms 
  k) Single and multiple-station heat alarms 
  l) Supervisory signal devices (except valve tamper switches) 
  m) Waterflow devices 
  n) Valve tamper switches 
   
16 Guard's tour equipment 
   
17 Interface equipment 
   
18 Special hazard equipment 
   
19 Alarm notification appliances   
  a) Audible devices 
  b) Audible textual notification appliances 
  c) Visible devices 
   
  COMPONENT  FLITIAL/ REACCEPTANCE MONTHLY  QUARTERLY  SEMI- ANNUALLY  ANNUALLY 
20 Off-premises transmission equipment 
   
21 Supervising station fire alarm systems - transmitters   
  a) Digital alarm communicator transmitter (DACT) 
  b) Digital alarm radio transmitter (DART) 
  c) McCulloh transmitter 
  d) Radio alarm transmitter (RAT) 
   
22 Special procedures 
   
23 Supervising station fire alarm systems - receivers  
  a) Digital alarm communicator receiver (DACR) 
  b) Digital alarm radio receiver (DARR) 
  c) McCulloh systems 
  d) Two-way RF multiplex 
  e) Radio alarm supervising station receiver (RASSR)
  f) Radio alarm repeater station receiver (RARSR) 
  g) Private microwave 

The inspection, testing and maintenance requirements that apply to your building’s fire alarm system start from the date of initial installation and continue on at specific intervals throughout the life of the system. What follows is a brief synopsis of some of the major requirements you need to be aware of.

Tampa Fire Alarm Notifications : Tampa Fire Alarm Tests, Inspections and Maintenance

In order to avoid unnecessary occupant response and potential injury to emergency response personnel, it is very important that all affected parties be notified prior to any scheduled testing of the fire alarm system [see NFPA 72(99), Sec. 7-1.3]. Those notified should include, but not be limited to, building occupants (e.g. visitors, staff and patients/residents) and the monitoring company or agency.

Tampa Fire Alarm New Installations : Tampa Fire Alarm Tests, Inspections and Maintenance

In order to meet both federal certification requirements and state licensure requirements, fire alarm systems are required to be installed in accordance with NFPA 72 and the requirements of NFPA 101 applicable to I-2 or healthcare occupancies NFPA 101(00), Sections 18/19.3.4 and 9.6.1.4]. All newly installed systems are required to be acceptance tested in accordance with the requirements of Chapter 7 of NFPA 72(99). Notify the fire code official prior to such testing.

Tampa Fire Alarm System Modifications : Tampa Fire Alarm Tests, Inspections and Maintenance

Reacceptance testing is required after any of the following occur [see NFPA 72(99), Sec. 7-1.6.2]:

The extent of testing necessary is determined as follows:

Tampa Fire Alarm Semi Annual Tests & Inspections
Tampa Fire Alarm Tests, Inspections and Maintenance

Certain fire alarm system components need to be visually inspected semiannually [see
NFPA 72(99), Table 7-3.1]. These visual inspections can be performed by facility staff and include:

Tampa Fire Alarm Annual Tests & Inspections
Tampa Fire Alarm Tests, Inspections and Maintenance

The entire system is required to be thoroughly inspected, tested and maintained each year by an approved servicing company in accordance with Chapter 7 of NFPA 72(99) [see NFPA 72(99), Tables 7-2.2, 7-3.1 and 7-3.2; NFPA 90A(99), Sec. 4-4.1]. Testing must include control equipment, remote annunciators, initiating devices, HVAC shutdown devices and alarm notification appliances.
Fire alarm interconnect switches on kitchen hood extinguishing systems are also required to be tested annually.
Inspection, testing and maintenance of batteries, smoke detectors (both system connected and battery-operated) and equipment used to transmit signals to a supervising station are covered later on in this guide.

Tampa Fire Alarm Long Term Tests & Inspections
Tampa Fire Alarm Tests, Inspections and Maintenance

Non restorable fixed-temperature, spot-type heat detectors are required to be replaced after 15 years from initial installation [see NFPA 72(99), Table 7-2.2, Item 13.d.3]. As an alternate, 2 detectors per 100 must be laboratory tested. If these detectors fail when tested, additional detectors must be tested to determine if the problem is a general or localized one.

Tampa Batteries
Batteries serving as a secondary power supply for fire alarm systems must be visually inspected at the following intervals to verify that they are free of damage* [see NFPA 72(99), Table 7-3.1, Item 3]:

Tampa Smoke Detectors
Battery-operated detectors
Some facilities have had battery-operated smoke detectors installed to meet the federal certification requirements of NFPA 101(00), Sections 18/19.7.5.2 – requirements that apply to buildings that are either unsprinklered or only partially sprinklered.

Tampa Hard-wired detectors
Hard-wired (including low voltage) automatic smoke detectors, including duct smoke detectors, must be visually inspected semiannually [see NFPA 72(99), Sec.7-3.1 and Table 7-3.1]. Exception: For listed addressable fire alarm systems that perform automatic inspections at a frequency of not less than weekly, the visual inspections are allowed to be conducted annually. The system would need to be capable of producing a print-out documenting these weekly inspections.
Hard-wired (including low voltage) smoke detectors must be sensitivity tested in
accordance with NFPA 72(99), Sec. 7-3.2.1. This section requires that detector sensitivity be checked within 1 year after installation and every other year thereafter.
Detectors found to have a sensitivity outside the listed and marked sensitivity range must be cleaned and recalibrated or be replaced. If, after the second test, detectors are found to have remained within their listed and marked sensitivity range (or 4 percent obscuration light gray smoke, if not marked), the length of time between sensitivity tests may be extended to a maximum of 5 years.
Something to keep in mind about detector testing: Smoke entry tests are required for functional and sensitivity testing of smoke detectors. Magnet tests do not replace smoke entry tests.

Tampa Fire Alarm Monitoring : Tampa UL Certified Central Station Monitoring

NFPA 101(00), Sec. 18/19.3.4.3.2 requires automatic fire department notification on activation of the building fire alarm system. This is typically accomplished by contracting with a company or agency that provides what’s called a central supervising station service. On receipt of a fire alarm signal from your facility, operators at the supervising station turn around and retransmit the signal to the local 9-1-1 communications center. In some locations, the local 9-1-1 communications center will accept fire alarm signals directly (this is called remote supervising station service).
The means of communication between your facility and the supervising station is required to be inspected and tested to ensure its reliability. The kind of testing required is based on the method of communication employed. NFPA 72 allows the use of a number of transmission technologies [see NFPA 72(99), Sec. 5-5.2.1.1] to include:

The method of communication most commonly employed at healthcare facilities is the Digital Alarm Communicator Transmitter (DACT) – also called an automatic dialer. For that reason, this guide will not address the other transmission technologies except to say that:

The DACT is a component at the facility that, upon receipt of a signal from the fire alarm control panel, seizes a connected telephone line, dials one of two pre-selected numbers to connect to the supervising station and transmits the necessary alarm, trouble or supervisory signal. One of the easiest ways to tell if you have a DACT is to check the communicator to see how many outgoing connections it has – a DACT requires two paths for transmitting fire alarm signal information.
FLUTION: NFPA 72(99), Sec. 5-5.3.2.1.1 only allows a DACT to be connected to a “loop start telephone circuit”. Such circuits employ copper lines that allow the local phone company to provide back-up power in case of a failure of the public utility power. The use of fiber-optic cable is, however, becoming more and more common.
A DACT cannot use fiber-optic cable and be code-compliant – in other words, if your facility’s phone system employs fiber-optic cable only, a different transmission technology will need to be used to communicate with the supervising station. Depending upon the technology chosen, quarterly testing of the transmission equipment may be required [see NFPA 72(99), Table 7-3.2].
Inspection and testing
DACTs are required to be visually inspected semiannually to verify that they are free of obvious damage and tested annually [see NFPA 72(99), Tables 7-3.1 and 7-3.2]. DACT testing requirements are detailed in NFPA 72(99), Table 7-2.2, Item 16 and include:

Documentation Requirements
Almost as important as conducting required inspections, testing and maintenance is documenting the fact that they occurred. NFPA 72 requires that these services be properly recorded.


Fire Service Pro © Fire Protection Company Websites

Fire Alarm Companies
Fire Protection Companies in Florida

Fire Protection Companies in the State of Florida

Florida Fire Protection Companies

Fire Protection Companies in the State of Florida

Alafaya, FL Fire Protection Jacksonville, FL Fire Protection
Apopka, FL Fire Protection Kendall, FL Fire Protection
Boca Raton, FL Fire Protection Lakeland, FL Fire Protection
Brandon, FL Fire Protection Largo, FL Fire Protection
Cape Coral, FL Fire Protection Melbourne, FL Fire Protection
Clearwater, FL Fire Protection Miami, FL Fire Protection
Coral Gables, FL Fire Protection Miramar, FL Fire Protection
Coral Springs, FL Fire Protection Orlando, FL Fire Protection
Davie, FL Fire Protection Pembroke Pines, FL Fire Protection
Daytona Beach, FL Fire Protection Plantation, FL Fire Protection
Fort Lauderdale, FL Fire Protection St. Petersburg, FL Fire Protection
Gainesville, FL Fire Protection Sunrise, FL Fire Protection
Hialeah, FL Fire Protection Tallahassee, FL Fire Protection
Hollywood, FL Fire Protection Tampa, FL Fire Protection

Fire Protection Engineering and Design Company for the State of Florida

Staley Consulting Inc.
www.fireproengineer.com

Staley Consulting Inc. designs and engineers all fire protection systems complete with Drafts, Drawings, Blueprints, AUTOCAD and 3-D designs that may be required to pass permits and inspections conducted by the State Fire Marshall, OSHA, Insurance Companies, Health Code Compliance and Fire Code Compliance Agencies. The addition of a Fire Protection P.E. to the A/E team allows the architect to show the client that questions and concerns regarding fire protection will be addressed professionally.

Our team has years of practical experience, carry NICET Level III Certifications, AUTOCAD Engineers, P.E. and Degrees in Computer Assisted Design and Drafting.

We specialize in design and engineering of wet, dry, deluge, preaction, special hazard sprinkler systems, fire protection systems, fire sprinkler systems, fire alarm systems, fire hydrants, fire pumps, standpipes, backflow preventers, fire suppression systems, restaurant kitchen suppression systems and the full fire protection systems that may be required for hospitals, schools, museums, libraries, churches, malls, stores, gas stations, fuel dispensing companies, industrial plants, factories, commercial and/or residential buildings.

We have designed fire protection systems for Universal Studios at Universal Orlando Resort ®, Walt Disney World ® MGM Studios, Westin Grand Imagine, The Paramount in Orlando FL, Cape Canaveral Air Force Station, United States Navy, United States Air Force, United States Army, City of Clermont (Florida), Dillard High School (Broward County, Florida), Daytona Beach College, 101 Eola, Publix, Mirabay Clubhouse, Oviedo Gymnasium & Aquatic Center, JetBlue, Verizon Wireless, Orlando Regional Medical Center, Saint Katharine Drexel Catholic Church, Seventh Day Adventist Church, Sandestin Luau, Habana Grill, Charley's Steakhouse to name projects.

We Carry the following Fire Protection Engineering Classifications in Florida

Assembly Occupancy Aviation Education Entertainment Government Industrial
Medical Military Mixed Use Office Religious Assemblies Residential Restaurants
Retail            
Design and Engineering the following Fire Protection Systems
Fire Protection Systems Fire Sprinkler Systems Fire Hydrants Fire Suppression Systems Standpipe Fire Sprinkler Systems Water Based Automatic Fire Sprinklers
  • Prepare Design Drawings
  • Hydraulic Calculations
  • Communicate with Officials on Local Fire Codes
  • Prepare Fire Protection Specifications
  • Fire Code Research
  • Field Site Visits
  • Construction Administration
  • Punch Lists
  • Answering RFI's
  • Provide Working Drawings Per NFPA 13
  • Shop Drawings & Review
  • Emergency Signage & Lighting
  • Evacuation Routes
  • Road Turn Arounds
  • Automatic Fire Sprinklers
  • Water Based
  • Standpipe Systems
  • Special Hazards
  • Fire Hydrants
  • Fire Pumps
  • Backflow Preventers
  • Design
  • Flow Testing
  • Determine Availability of Water Supply
  • Engineering
  • Fire Hydrant Testing
  • Restaurant Kitchen Suppression Systems
    • Restaurant kitchen hood suppression systems
  • Auto Body or Paint Spray Booth Fire Suppression Systems
  • Data Centers Fire Suppression Systems
  • Kitchen fire protection systems
  • Clean agent fire suppression systems
    • Carbon dioxide fire suppression systems
    • Data centers, computer rooms, file storage facilities
  • Wet standpipe fire sprinklers
  • Dry standpipe fire sprinklers
  • Combined standpipe fire sprinklers
  • Standpipe hose connections
  • Temporary Standpipes
  • Standpipe fire sprinklers
  • Wet pipe automatic fire sprinklers
  • Dry pipe automatic fire sprinklers
  • Deluge automatic fire sprinklers
  • Combined automatic fire sprinklers
  • Pre-Action automatic fire sprinklers

Fire Protection Companies in the United States

Fire Protection Companies in the United States

Baltimore, MD Buffalo, NY Las Vegas, NV Markham, Canada Orange County, CA
Sacramento, CA San Diego, CA San Diego, CA Tampa, FL Toronto, Canada
Los Angeles, CA Fire Protection Engineering     Vaughan, Canada

 

Contact Us to Build a Fire Protection Website in Your City.