NFPA 10: Standard for Portable Fire Extinguishers in Tampa

NFPA 10: Fire Extinguisher Tests, Inspections & Maintenance in Tampa

NFPA 101(00), Sec. 9.7.4.1 require that portable fire extinguishers be inspected and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers. NFPA 101(00), Sec. 2.1.1 references the 1998 edition of NFPA 10.

NFPA Standards and Codes in Tampa

Visit NFPA to purchase the newest version of the NFPA 10 standards and codes.

Tampa Portable Fire Extinguisher Visual Inspections

Portable fire extinguishers are required to be visually inspected when initially placed in service and at least monthly thereafter [see NFPA 10(98), Sections 4-3.1]. These visual inspections, intended to help ensure that each extinguisher is in its designated place and will operate if needed, can be performed by facility staff.
A pressure gauge in the “normal” or “operable” range is not a 100 percent guaranty that the extinguisher will perform as intended. A broken seal, for example, may be an indication that someone has used the extinguisher and discharged a portion of the contents too small to affect the pressure gauge. NFPA 10(98), Sec. 4-3.2, therefore, requires that the monthly inspection verify a number of things including:

Examples of such circumstances might include extinguishers that are oftentimes found obstructed during monthly inspections or extinguishers located in areas where they are subject to tampering, theft or mechanical injury. Obviously, any problems found during the monthly inspection must be corrected immediately. Some problems trigger a need for full maintenance or even replacement of the extinguisher. For example:

Tampa Portable Fire Extinguisher Annual Tests, Inspections and Maintenance

“Maintenance” is a thorough examination and repair, as needed, of your facility’s portable fire extinguishers and is covered in NFPA 10(98), Sec. 4-4. Maintenance is required at least once a year – more frequently when indicated by a routine monthly inspection, as discussed earlier. Maintenance is also required whenever extinguishers undergo hydrostatic testing. Because maintenance is required to include a thorough examination of the mechanical parts, extinguishing agent and expelling means of each portable fire extinguisher, it must be performed by an approved extinguisher servicing company. A more detailed look at what annual maintenance entails can be found in NFPA 10(98), Tables A-4-4.4.2(a) and A-4-4.4.2(b). It should be noted that new tamper seals are required to be installed whenever maintenance is performed on rechargeable fire extinguishers [see NFPA 10(98), Sec. 4-4.2.1].

Tampa Portable Fire Extinguisher Six (6) Year Tests, Inspections and Maintenance

Every 6 years, stored pressure fire extinguishers that require a 12-year hydrostatic test (e.g. dry chemical extinguishers) must be emptied and proper maintenance procedures performed [see NFPA 10(98), Sec. 4-4.3]. The exception to this rule is non-rechargeable extinguishers, which are required to be removed from service 12 years from the date of manufacture. Again, this maintenance must be performed by an approved extinguisher servicing company.

Tampa Portable Fire Extinguisher Hydrostatic Tests, Inspections and Maintenance

At certain intervals, fire extinguishers are required to be pressure tested using water or some other non-compressible fluid to help prevent unwanted failure or rupture of the cylinder [see NFPA 10(98), Chapter 5]. This is called hydrostatic testing and includes both an internal and external examination of the cylinder. Because this testing requires special training and equipment, it needs to be performed by an approved extinguisher servicing company.
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(98), Sec. 5-2 and Table 5-2. Test intervals for some of the most commonly found extinguishers are as follows:

As mentioned earlier, the exception to the rule for hydrostatic testing is no rechargeable stored pressure extinguishers (e.g. dry chemical extinguishers), which are required to be removed from service 12 years from the date of manufacture.
Information only:
Some of you may have heard…
The 2007 edition of NFPA 10 contains a new requirement for the removal of dry chemical extinguishers manufactured prior to October, 1984 [see NFPA 10(07), Sec. 4.4.1]. Removal is to occur at the time of the next 6-year maintenance interval or next hydro test interval, whichever comes first. This requirement came about as the result of significant changes made to UL Standard 299, Dry Chemical Fire Extinguishers, based on fire testing conducted by UL, FEMA and NFPA.
Documentation Requirements
Almost as important as conducting required inspection, testing and maintenance is documenting the fact that it occurred. NFPA 10 requires that these services be properly recorded.

Tampa Hydrostatic Tests and Inspections

All commercial and industrial business owners shall assure that hydrostatic testing is performed by trained persons with suitable testing equipment and facilities. The commercial and industrial business owners shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions:

In addition to an external visual examination, the commercial and industrial business owners shall assure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests. In addition to an external visual examination, the commercial and industrial business owners shall assure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests. OSHA (Occupational Safety and Health Standards) Fire Protection: Portable fire extinguishers
TABLE L-1


Type of extinguishers

Test interval (years)

Soda acid (soldered brass shells) (until 1/1/82)
Soda acid (stainless steel shell)
Cartridge operated water and/or antifreeze
Stored pressure water and/or antifreeze
Wetting agent
Foam (soldered brass shells) (until 1/1/82)
Foam (stainless steel shell)
Aqueous Film Forming foam (AFFF)
Loaded stream
Dry chemical with stainless steel
Carbon Dioxide
Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells
Dry chemical, cartridge or cylinder operated, with mild steel shells
Halon 1211
Halon 1301
Dry powder, cartridge or cylinder operated with mild steel shells

(1)
5
5
5
5
(1)
5
5
5
5
5
12

12
12
12
12

1Extinguishers having shells constructed of copper or brass joined by soft solder or rivets shall not be hydrostatically tested and shall be removed from service by January 1, 1982. (Not permitted)


Fire Service Pro © Fire Protection Company Websites

Fire Extinguisher Companies
Fire Protection Companies in Florida

Fire Protection Companies in the State of Florida

Florida Fire Protection Companies

Fire Protection Companies in the State of Florida

Alafaya, FL Fire Protection Jacksonville, FL Fire Protection
Apopka, FL Fire Protection Kendall, FL Fire Protection
Boca Raton, FL Fire Protection Lakeland, FL Fire Protection
Brandon, FL Fire Protection Largo, FL Fire Protection
Cape Coral, FL Fire Protection Melbourne, FL Fire Protection
Clearwater, FL Fire Protection Miami, FL Fire Protection
Coral Gables, FL Fire Protection Miramar, FL Fire Protection
Coral Springs, FL Fire Protection Orlando, FL Fire Protection
Davie, FL Fire Protection Pembroke Pines, FL Fire Protection
Daytona Beach, FL Fire Protection Plantation, FL Fire Protection
Fort Lauderdale, FL Fire Protection St. Petersburg, FL Fire Protection
Gainesville, FL Fire Protection Sunrise, FL Fire Protection
Hialeah, FL Fire Protection Tallahassee, FL Fire Protection
Hollywood, FL Fire Protection Tampa, FL Fire Protection

Fire Protection Engineering and Design Company for the State of Florida

Staley Consulting Inc.
www.fireproengineer.com

Staley Consulting Inc. designs and engineers all fire protection systems complete with Drafts, Drawings, Blueprints, AUTOCAD and 3-D designs that may be required to pass permits and inspections conducted by the State Fire Marshall, OSHA, Insurance Companies, Health Code Compliance and Fire Code Compliance Agencies. The addition of a Fire Protection P.E. to the A/E team allows the architect to show the client that questions and concerns regarding fire protection will be addressed professionally.

Our team has years of practical experience, carry NICET Level III Certifications, AUTOCAD Engineers, P.E. and Degrees in Computer Assisted Design and Drafting.

We specialize in design and engineering of wet, dry, deluge, preaction, special hazard sprinkler systems, fire protection systems, fire sprinkler systems, fire alarm systems, fire hydrants, fire pumps, standpipes, backflow preventers, fire suppression systems, restaurant kitchen suppression systems and the full fire protection systems that may be required for hospitals, schools, museums, libraries, churches, malls, stores, gas stations, fuel dispensing companies, industrial plants, factories, commercial and/or residential buildings.

We have designed fire protection systems for Universal Studios at Universal Orlando Resort ®, Walt Disney World ® MGM Studios, Westin Grand Imagine, The Paramount in Orlando FL, Cape Canaveral Air Force Station, United States Navy, United States Air Force, United States Army, City of Clermont (Florida), Dillard High School (Broward County, Florida), Daytona Beach College, 101 Eola, Publix, Mirabay Clubhouse, Oviedo Gymnasium & Aquatic Center, JetBlue, Verizon Wireless, Orlando Regional Medical Center, Saint Katharine Drexel Catholic Church, Seventh Day Adventist Church, Sandestin Luau, Habana Grill, Charley's Steakhouse to name projects.

We Carry the following Fire Protection Engineering Classifications in Florida

Assembly Occupancy Aviation Education Entertainment Government Industrial
Medical Military Mixed Use Office Religious Assemblies Residential Restaurants
Retail            
Design and Engineering the following Fire Protection Systems
Fire Protection Systems Fire Sprinkler Systems Fire Hydrants Fire Suppression Systems Standpipe Fire Sprinkler Systems Water Based Automatic Fire Sprinklers
  • Prepare Design Drawings
  • Hydraulic Calculations
  • Communicate with Officials on Local Fire Codes
  • Prepare Fire Protection Specifications
  • Fire Code Research
  • Field Site Visits
  • Construction Administration
  • Punch Lists
  • Answering RFI's
  • Provide Working Drawings Per NFPA 13
  • Shop Drawings & Review
  • Emergency Signage & Lighting
  • Evacuation Routes
  • Road Turn Arounds
  • Automatic Fire Sprinklers
  • Water Based
  • Standpipe Systems
  • Special Hazards
  • Fire Hydrants
  • Fire Pumps
  • Backflow Preventers
  • Design
  • Flow Testing
  • Determine Availability of Water Supply
  • Engineering
  • Fire Hydrant Testing
  • Restaurant Kitchen Suppression Systems
    • Restaurant kitchen hood suppression systems
  • Auto Body or Paint Spray Booth Fire Suppression Systems
  • Data Centers Fire Suppression Systems
  • Kitchen fire protection systems
  • Clean agent fire suppression systems
    • Carbon dioxide fire suppression systems
    • Data centers, computer rooms, file storage facilities
  • Wet standpipe fire sprinklers
  • Dry standpipe fire sprinklers
  • Combined standpipe fire sprinklers
  • Standpipe hose connections
  • Temporary Standpipes
  • Standpipe fire sprinklers
  • Wet pipe automatic fire sprinklers
  • Dry pipe automatic fire sprinklers
  • Deluge automatic fire sprinklers
  • Combined automatic fire sprinklers
  • Pre-Action automatic fire sprinklers

Fire Protection Companies in the United States

Fire Protection Companies in the United States

Baltimore, MD Buffalo, NY Las Vegas, NV Markham, Canada Orange County, CA
Sacramento, CA San Diego, CA San Diego, CA Tampa, FL Toronto, Canada
Los Angeles, CA Fire Protection Engineering     Vaughan, Canada

 

Contact Us to Build a Fire Protection Website in Your City.