Home Fire Sprinklers Fire Alarms Fire Extinguishers Fire Suppression  

Fire Suppression Services

Florida Fire Service, Inc.

Fire Suppression Tampa

Tampa Fire Suppression
Tampa Fire Suppression

Class A, B, C and D Fires
Class A, B, C and D Fires

Tampa NFPA 12 Carbon Dioxide Fire Suppression Tests and Inspections

NFPA 12 + 17 Fire Suppression Inspections, Tests & Maintenance in Tampa

NFPA 101(00), Sec. 9.2.3 requires that commercial cooking equipment be in accordance with NFPA
96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. NFPA
101(00), Sec. 2.1.1 references the 1998 edition of the standard. NFPA 96(98), in turn, references four
other NFPA standards applicable to automatic fire-extinguishing systems installed to protect kitchen
hood systems and cooking equipment [see NFPA 96(98), Sections 7-2.2.1 and 12-1]:
• NFPA 12(98), Standard on Carbon Dioxide Extinguishing Systems
• NFPA 13(96), Standard for the Installation of Sprinkler Systems
• NFPA 17(98), Standard for Dry Chemical Extinguishing Systems
• NFPA 17A(98), Standard for Wet Chemical Extinguishing Systems

Tampa NFPA 17 Fire Suppression Tests and Inspections

Dry Chemical Fire Suppression Inspections, Tests and Maintenance in Tampa

Dry chemical fire suppression systems provide protection for many flammable and combustible liquid (Class B) fire hazards. They are particularly suited for outdoor environments where concerns about freezing prevent the installation of water-based systems.
The system owner is responsible for a monthly inspection to ensure the equipment remains in an operable condition. The inspection must be conducted in accordance with the manufacturer’s listed installation and maintenance manual or owner’s manual.
The inspection should include a check of the following components to verify that:

The inspection date and the initials of the person performing the inspection should be recorded, and the records maintained until the next semiannual service.
At least semiannually, maintenance shall be conducted in accordance with the manufacturer’s listed installation and maintenance manual. This maintenance should include

If there is evidence of caking, the dry chemical must be discarded and the system recharged in accordance with the manufacturer’s instructions.
For additional information, refer to the National Fire Protection Association (NFPA) 17, Standard for Dry Chemical Extinguishing Systems.

Tampa Restaurant Kitchen Hood Fire Suppression Systems Inspections, Tests and Maintenance

The entire exhaust system (hood, grease removal devices, fans and ducts) for kitchen cooking equipment needs to be thoroughly inspected at least every 6 months to ensure that it’s free of grease accumulations [see NFPA 96(98), Sec. 8-3.1 and Table 8-3.1]. This inspection must be conducted by a company or person properly trained and qualified to perform such a service. The authority having jurisdiction (AHJ) may require a certificate or other proof of such training.
If this inspection reveals deposits from grease-laden vapors, the entire exhaust system must be cleaned to bare metal by a properly trained, qualified and certified company or person(s) acceptable to the AHJ [see NFPA 96(98), Sec. 8-3.1.1]. It should be noted that:

When the cleaning process is completed:

Tampa Kitchen hood fire-extinguishing system
The standards applicable to automatic dry- or wet-chemical fire-extinguishing systems protecting kitchen cooking equipment [see NFPA 17(98), Sec. 9-2.1/NFPA 17A(98), Sec. 5-2.1] require that such systems be inspected monthly to ensure that:

In addition, an inspection and servicing of the kitchen hood fire-extinguishing system by properly trained and qualified persons is required at least every 6 months [see NFPA 96(98), Sec. 8-2].

Fire alarm interconnect switches are required to be tested annually by mechanically or electrically operating the switch to verify receipt of a signal at the fire alarm control panel [see NFPA 72(99), Tables 7-3.2 and 7-2.2]. This testing should be performed as part of the annual test conducted of the building fire alarm system. The equipment manufacturer may have additional maintenance requirements that should be followed in order to ensure proper operation of the system and maintain applicable warranties. The standards applicable to automatic dry- or wet-chemical fire-extinguishing systems also contain inspection requirements that must be followed, including:

Tampa Fire Suppression Hydrostatic Tests, Inspections and Maintenance

DOCUMENT Your Tests, Inspections and Service
Exhaust system:
Both NFPA 96 many state fire codes require that exhaust system cleanings be recorded [see NFPA 96(98]. These records must include the extent, time and date of cleaning. When a vent cleaning contractor is used, the contractor must be able to provide you with a certificate showing the date of any inspections or cleanings performed. In addition, the contractor is required to display a tag within the kitchen indicating the date of the cleaning and the name of the servicing company and identifying any areas that were not cleaned on the date of the service.

Fire Protection Systems that Require Scheduled Tests, Inspections and Maintenance in Tampa

Types of Fire Prevention Systems Requiring Tests and Inspections

Sprinkler and Standpipe Systems.
Engineered CO2 fire suppression systems.
Engineered clean agent fire suppression systems.
Engineered foam fire suppression systems.
Engineered dry chemical fire suppression systems.
Engineered water mist fire suppression systems.
Residential fire suppression systems (NFPA 13D systems)
Pre-engineered CO2 fire suppression systems only.
Pre-engineered clean agent fire suppression systems only.
Pre-engineered foam fire suppression systems only.
Pre-engineered dry chemical fire suppression systems only.
Pre-engineered wet chemical fire suppression systems only.
Pre-engineered water mist suppression systems.

Tampa Special Agent Extinguishing Systems Test and Inspection Checklist

When your fire Special Agent Extinguishing Systems is tested, inspected or serviced by local fire departments, state licensed fire protection companies, certified fire protection technicians and/or fire safety engineers. They may use a form from NFPA similiar to the one below when a test, inspection or service is completed for your Special Agent Extinguishing System.

Tampa NFPA Standards and Codes

For a new versions visit NFPA Tests and Inspections Forms

Inspection Checklist
Special Agent Extinguishing Systems
Building: ______________________________________________________________________
Address: ______________________________________________________________________
Inspector: ___________________________________ Date: ___________________________
Date of Last Inspection: _____________________ Outstanding Violations: Yes No
General
Type of special agent extinguishing system:
❑ Wet chemical
❑ Dry chemical
❑ Halon
❑ Carbon dioxide
❑ Other: ________________________________________
What does the system protect? _____________________________________________________
Date system installed: ______________________________
Were building alterations/renovations made since
last inspection? ❑ Yes ❑ No
Was a new special agent extinguishing system added
since last inspection? ❑ Yes ❑ No
Was any system alteration made since last inspection? ❑ Yes ❑ No
Is system connected to building fire alarm? ❑ Yes ❑ No ❑ N/A*
Automatic Shutdown
What is fuel source?
❑ Electricity
❑ Gas
❑ Other: _______________________________________
Nozzles
Are caps in place? ❑ Yes ❑ No ❑ N/A
Are nozzles properly oriented to protect hazard? ❑ Yes ❑ No ❑ N/A
Are there signs of damage? ❑ Yes ❑ No ❑ N/A
Manual Releases
Are manual releases clear and unobstructed? ❑ Yes ❑ No ❑ N/A
Are they properly identified? ❑ Yes ❑ No ❑ N/A
System Pressure Gauges
Are system pressure gauges in proper operating range? ❑ Yes ❑ No ❑ N/A
Are they readily visible? ❑ Yes ❑ No ❑ N/A
*N/A (not applicable) means there’s no such feature in the building.
Form A-12 Inspection Checklist to Accompany Chapter 17
Copyright © 2002 National Fire Protection Association (Page 1 of 2)
611
Gaseous Agent Systems (Halon or CO2)
Are room doors self-closing or automatic closing? ❑ Yes ❑ No ❑ N/A
Quarterly Inspections and Tests
Are quarterly inspections and tests recorded? ❑ Yes ❑ No
Semiannual Inspections and Tests
Are semiannual inspections and tests recorded? ❑ Yes ❑ No
Annual Inspections and Tests
Are annual inspections and tests recorded? ❑ Yes ❑ No
5-Year Tests
Are 5-year tests recorded? ❑ Yes ❑ No ❑ N/A
• Were CO2 system hoses tested? ❑ Yes ❑ No ❑ N/A
12-Year Tests
Are 12-year tests recorded? ❑ Yes ❑ No ❑ N/A
• Were CO2 system cylinders tested? ❑ Yes ❑ No ❑ N/A
• Were CO2 systems discharge tested? ❑ Yes ❑ No ❑ N/A
Notes: ________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
Form A-12 Continued
Copyright © 2002 National Fire Protection Association (Page 2 of 2)

Tampa Clean Agent Extinguishing Systems Test and Inspection Checklist

Tampa NFPA Standards and Codes

For a new versions visit NFPA Tests and Inspections Forms

Inspection Checklist
Clean Agent Extinguishing Systems
Building: ______________________________________________________________________
Address: ______________________________________________________________________
Inspector: __________________________ Date: _____________________________________
Date of Last Inspection: _____________________ Outstanding Violations: Yes No
General
Agent type: ____________________________________________________________________
Clean agent extinguishing system protects:____________________________________________
Date system installed: ____________________________________________________________
Were building alterations/renovations made since
last inspection? ❑ Yes ❑ No
Was new clean agent extinguishing system added since
last inspection? ❑ Yes ❑ No
Was any system alteration made since last inspection? ❑ Yes ❑ No
Is system connected to building fire alarm? ❑ Yes ❑ No ❑ N/A*
Automatic Shutdown
What is fuel source?
❑ Electricity
❑ Gas
❑ Other: __________________________________________
Nozzles
Are caps in place? ❑ Yes ❑ No ❑ N/A
Are nozzles properly oriented to protect hazard? ❑ Yes ❑ No ❑ N/A
Are there signs of damage? ❑ Yes ❑ No ❑ N/A
Manual Releases
Are manual releases clear and unobstructed? ❑ Yes ❑ No ❑ N/A
Are they properly identified? ❑ Yes ❑ No ❑ N/A
System Pressure Gauges
Are system pressure gauges in proper operating range? ❑ Yes ❑ No ❑ N/A
Are they readily visible? ❑ Yes ❑ No ❑ N/A
Room Doors
Are room doors self-closing or automatic closing? ❑ Yes ❑ No ❑ N/A
Quarterly Inspections and Tests Recorded
Are quarterly inspections and tests recorded? ❑ Yes ❑ No
*N/A (not applicable) means there’s no such feature in the building.
Form A-13 Inspection Checklist to Accompany Chapter 18
Copyright © 2002 National Fire Protection Association (Page 1 of 2)
613
Semiannual Inspections and Tests Recorded
Are semiannual inspections and tests recorded? ❑ Yes ❑ No
Annual Inspections and Tests Recorded
Are annual inspections and tests recorded? ❑ Yes ❑ No
5-Year Tests
Are 5-year tests recorded? ❑ Yes ❑ No ❑ N/A
• Were system hoses tested? ❑ Yes ❑ No ❑ N/A
Notes: _______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
Form A-13 Continued
Copyright © 2002 National Fire Protection Association (Page 2 of 2)

Tampa Portable Fire Extinguishers Test and Inspection Checklist

Tampa NFPA Standards and Codes

For a new versions visit NFPA Tests and Inspections Forms

Inspection Checklist
Portable Fire Extinguishers
Building: _____________________________________________________________________
Address: _____________________________________________________________________
Inspector: _________________________ Date: _____________________________________
Date of Last Inspection: ________________________ Outstanding Violations: Yes No
General
Are fire extinguishers provided? ❑ Yes ❑ No
Mounting
Are extinguishers properly mounted? ❑ Yes ❑ No
Are any extinguishers blocked? ❑ Yes ❑ No
Does distribution appear adequate? ❑ Yes ❑ No
Monthly Inspections
Are monthly inspections recorded? ❑ Yes ❑ No ❑ N/A*
• On tag on extinguisher? ❑ Yes ❑ No ❑ N/A
• On form? ❑ Yes ❑ No ❑ N/A
Annual Maintenance
Are records provided of annual maintenance? ❑ Yes ❑ No
*N/A (not applicable) means there’s no such feature in the building.
Notes: _______________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
Form A-14 Inspection Checklist to Accompany Chapter 19


Fire Service Pro © Fire Protection Company Websites

Fire Suppression Companies
Fire Protection Companies in Florida

Fire Protection Companies in the State of Florida

Florida Fire Protection Companies

Fire Protection Companies in the State of Florida

Alafaya, FL Fire Protection Jacksonville, FL Fire Protection
Apopka, FL Fire Protection Kendall, FL Fire Protection
Boca Raton, FL Fire Protection Lakeland, FL Fire Protection
Brandon, FL Fire Protection Largo, FL Fire Protection
Cape Coral, FL Fire Protection Melbourne, FL Fire Protection
Clearwater, FL Fire Protection Miami, FL Fire Protection
Coral Gables, FL Fire Protection Miramar, FL Fire Protection
Coral Springs, FL Fire Protection Orlando, FL Fire Protection
Davie, FL Fire Protection Pembroke Pines, FL Fire Protection
Daytona Beach, FL Fire Protection Plantation, FL Fire Protection
Fort Lauderdale, FL Fire Protection St. Petersburg, FL Fire Protection
Gainesville, FL Fire Protection Sunrise, FL Fire Protection
Hialeah, FL Fire Protection Tallahassee, FL Fire Protection
Hollywood, FL Fire Protection Tampa, FL Fire Protection

Fire Protection Engineering and Design Company for the State of Florida

Staley Consulting Inc.
www.fireproengineer.com

Staley Consulting Inc. designs and engineers all fire protection systems complete with Drafts, Drawings, Blueprints, AUTOCAD and 3-D designs that may be required to pass permits and inspections conducted by the State Fire Marshall, OSHA, Insurance Companies, Health Code Compliance and Fire Code Compliance Agencies. The addition of a Fire Protection P.E. to the A/E team allows the architect to show the client that questions and concerns regarding fire protection will be addressed professionally.

Our team has years of practical experience, carry NICET Level III Certifications, AUTOCAD Engineers, P.E. and Degrees in Computer Assisted Design and Drafting.

We specialize in design and engineering of wet, dry, deluge, preaction, special hazard sprinkler systems, fire protection systems, fire sprinkler systems, fire alarm systems, fire hydrants, fire pumps, standpipes, backflow preventers, fire suppression systems, restaurant kitchen suppression systems and the full fire protection systems that may be required for hospitals, schools, museums, libraries, churches, malls, stores, gas stations, fuel dispensing companies, industrial plants, factories, commercial and/or residential buildings.

We have designed fire protection systems for Universal Studios at Universal Orlando Resort ®, Walt Disney World ® MGM Studios, Westin Grand Imagine, The Paramount in Orlando FL, Cape Canaveral Air Force Station, United States Navy, United States Air Force, United States Army, City of Clermont (Florida), Dillard High School (Broward County, Florida), Daytona Beach College, 101 Eola, Publix, Mirabay Clubhouse, Oviedo Gymnasium & Aquatic Center, JetBlue, Verizon Wireless, Orlando Regional Medical Center, Saint Katharine Drexel Catholic Church, Seventh Day Adventist Church, Sandestin Luau, Habana Grill, Charley's Steakhouse to name projects.

We Carry the following Fire Protection Engineering Classifications in Florida

Assembly Occupancy Aviation Education Entertainment Government Industrial
Medical Military Mixed Use Office Religious Assemblies Residential Restaurants
Retail            
Design and Engineering the following Fire Protection Systems
Fire Protection Systems Fire Sprinkler Systems Fire Hydrants Fire Suppression Systems Standpipe Fire Sprinkler Systems Water Based Automatic Fire Sprinklers
  • Prepare Design Drawings
  • Hydraulic Calculations
  • Communicate with Officials on Local Fire Codes
  • Prepare Fire Protection Specifications
  • Fire Code Research
  • Field Site Visits
  • Construction Administration
  • Punch Lists
  • Answering RFI's
  • Provide Working Drawings Per NFPA 13
  • Shop Drawings & Review
  • Emergency Signage & Lighting
  • Evacuation Routes
  • Road Turn Arounds
  • Automatic Fire Sprinklers
  • Water Based
  • Standpipe Systems
  • Special Hazards
  • Fire Hydrants
  • Fire Pumps
  • Backflow Preventers
  • Design
  • Flow Testing
  • Determine Availability of Water Supply
  • Engineering
  • Fire Hydrant Testing
  • Restaurant Kitchen Suppression Systems
    • Restaurant kitchen hood suppression systems
  • Auto Body or Paint Spray Booth Fire Suppression Systems
  • Data Centers Fire Suppression Systems
  • Kitchen fire protection systems
  • Clean agent fire suppression systems
    • Carbon dioxide fire suppression systems
    • Data centers, computer rooms, file storage facilities
  • Wet standpipe fire sprinklers
  • Dry standpipe fire sprinklers
  • Combined standpipe fire sprinklers
  • Standpipe hose connections
  • Temporary Standpipes
  • Standpipe fire sprinklers
  • Wet pipe automatic fire sprinklers
  • Dry pipe automatic fire sprinklers
  • Deluge automatic fire sprinklers
  • Combined automatic fire sprinklers
  • Pre-Action automatic fire sprinklers

Fire Protection Companies in the United States

Fire Protection Companies in the United States

Baltimore, MD Buffalo, NY Las Vegas, NV Markham, Canada Orange County, CA
Sacramento, CA San Diego, CA San Diego, CA Tampa, FL Toronto, Canada
Los Angeles, CA Fire Protection Engineering     Vaughan, Canada

 

Contact Us to Build a Fire Protection Website in Your City.